5.1.7 Error and warning behavior
The monitoring of the analog input signal necessary accordin
to the application is to
be configured via the parameter
Error/Warning behavior 563.
Operation mode Function
0 -Off The input signal is not monitored.
1 -Warning < 1 V / 2 mA
If the input signal is less than 1 V or 2 mA, there
is a warning message.
2 -Shutdown < 1 V / 2 mA
If the input signal is less than 1 V or 2 mA, there
is a warning message, the drive mechanism is
decelerated according to stopping behavior 1.
3 -
Fault switch-off
< 1 V / 2 mA
If the input signal is less than 1 V or 2 mA, there
is a warning and fault message and the drive
mechanism stops freely.
he monitorin
of the analo
input si
nal is active independent of the release of the
frequency inverter according to the operation mode selected.
In operation mode 2, the drive mechanism is decelerated independent of the stoppin
behavior set (Parameter Operation mode 630) accordin
to stoppin
behavior 1
(shutdown and switch-off). If the set holding time has expired, there is a fault mes-
sage. A repeat start of the drive mechanism is possible by switchin
the start si
nal on
and off if the fault has been cleared.
Operation mode 3 defines the free stoppa
e of the drive mechanism, independent o
the stopping behavior selected, which is stipulated with the parameter Stop function
630.
Attention!
Monitoring of the analog input signal via the parameter
rror/Warnin
Behavior
563 demands a check of the characteristic parameters.
5.1.8 Adjustment
As a result of component tolerances, it can be necessary to ad
ust the analo
input.
Parameter
Adjustment 568 is used for this purpose.
Operation mode Function
0 -no adjustment Normal operation
1 -Adjustment 0 V / 0 mA
Adjustment of the measurement with an analog
signal of 0 V or 0 mA.
2 -Adjustment 10 V / 20 mA
Adjustment of the measurement with an analog
signal of 10 V or 20 mA.
Example of the adjustment of the analog input with a voltage signal:
Note: The measurements for the adjustment are to be done with a suitable
measuring instrument and the correct polarity.
If not, faulty measurements can result.
• Apply 0 V to the analo
input; e.
. with a wired link from the socket of the analo
input X410B.4 to socket X210B.7 (earth/GND) of the frequency inverter.
• Select operation mode "1 - Adjustment 0 V / 0 mA“.
• Apply 10 V to the analog input, e.g. with a wired link from the socket of the ana-
log input to socket X210B.5 (reference output 10 V) of the frequency inverter.
• Select operation mode "2 - Adjustment 10 V / 20 mA“.