20
ACT401- 43 45 47 49
Size 7 (-, A)
Output, motor side
Recommended rated motor power P
n
kW 75.0 90.0 110.0 132.0
Rated motor current output I
n
A 150.0 180.0 210.0 250.0
Rated motor voltage output U
n
V 3 x (from 0 to mains voltage)
Overload current for 60 s I
pk
A 225.0 270.0 315.0 332.0
Overload current for 1 s I
pk
A 270.0 325.0 375.0 375.0
Switching frequency f
c
kHz From 2 to 8
Rated motor frequency f
n
Hz From 0 to 1000
Input, mains side
Nominal mains voltage U V 320 ... 528
Nominal mains frequency f Hz 45 ... 66
Nominal current 3 ph/PE I A 143 172 208 249
Mains fuses 3 ph/PE I A 160 200 250 315
General
Short circuit / ground fault protection - - Yes, unlimited
Mounting position - - Vertical
Protection class - - IP 20 (EN60529)
(0)
Dimensions Std. A
HxWxD
mm 510 x 412 x 351
Cold Plate Opt. C
HxWxD
mm —
Weight (approx.) m kg 45 48
Environment
Cooling temperature T
n
°C From0to40(3K3DINIEC721-3-3)
Relative air humidity - % From 15 to 85, non-condensing
Derating P -
2.5%/Kabove40°C;Tmax=55°C;
5%/1000mabove1000minstallationaltitude;hmax=4000m
Options & accessories
Line choke - - External (depending on mains supply)
EMI filter - - External
Brake unit - - Optional internal brake transistor
Digital control unit - - Yes
Note: (0) = for protection classes higher than IP20 consult your local Bonfiglioli Drives Service Center
ACT401 - Technical data (from 75 to 132 kW)
Продается в России?
honjj