Mains voltage
3 x 480V~ maximum +10%
Nominal current
8A ... 40A
Frequency
50/60 Hz
Operating and storage temperature
-25°C...+100°C(climateclassacc.toCEI25/100/21)
Ambient temperature
+40°Cmaximum
Protection class
IP00
Connection type
Contact-protected terminals
Strand connection on load side (only up to ACT 401-18)
Metal fasteners are included in the supply
Note
These mains filters are installed between the line
choke and the frequency inverter. The frequency
inverter installed on the EMI filter must be
connected to the metal baseplate with a short, large
section earth connection.
Overload capacity is 1.5 times rated current for 1
minute, every 30 minutes.
Backplate EMI filters
Bonfiglioli Inverter
Bonfiglioli
EMI filter
Rated
current
Leakage
current
Power
dissipation
Weight
Size Type [A] [mA] [W] [kg]
1
ACT 201-05
FTV007B 8 5 10
1.5
ACT 201-07
ACT 201-09
ACT 401-05
ACT 401-07
ACT 401-09
ACT 401-11
2
ACT 201-11
ACT 401-12
ACT 401-13
ACT 401-15
ACT 401-18
3
ACT 401-19
FTV018B 18 1.2 10 3.5
ACT 401-21
4
ACT 401-23
FTV040B 40 1.2 10 3.5
ACT 401-25