44
110: Simple Sensorless Control
111: Simple Sensorless Control with PI function
115: Simple Sensorless Control with master / slave
control
116: Simple Sensorless Control with
synchronisation control
160: Simple Sensorless Control with Brake Control
and Load Detection
210: Field-oriented control with speed sensor
211: Field-oriented control with speed sensor and
PI function
215: Field-oriented control with speed sensor with
master / slave function
216: Field-oriented control with speed sensor with
electric shaft
230: Field-oriented control with speed sensor with
torque/speed switching
260: Field-oriented control with speed sensor with
Brake Control and Load Detection
410: Sensorless Control with extended tuning
411: Sensorless field orientation control with PI
regulator
415: Sensorless field orientation control with
electronic gearbox and position control
430: Sensorless Control with extended tuning and
torque / speed control switching
460: Sensorless Control with extended tuning and
with Brake Control and Load Detection
510: Sensorless field orientation control of a
synchronous machine
515: Sensorless field orientation control of a
synchronous machine with electronic gear and
position control
516: Sensorless field orientation control of a
synchronous machine with electronic gear and
index control
530: Sensorless field orientation control of a
synchronous machine with torque/speed
switching
560: Sensorless field orientation control of a
synchronous machine with electronic gear and
position control
By default the ACT frequency inverter is supplied
with configuration 110.
Configurations can be changed from the control
unit or PC (VPlus) by means of parameter P030.
Configuration 110 is recommended for low
dynamic applications or for speed control of
several motors in parallel (in the event that the
inverter selection criterion is based on the sum of
the rated currents of the motors to be driven).
Configuration 111 is recommended for driving
turbine machinery (pumps and fans).
Configuration 410 provides high dynamic
performance also at low speed without the use
of a speed sensor. For enhanced performance
the motor data must be entered and the system
must be tuned; in addition, the speed controller
must be set up for the optimisation of dynamic
performance in accordance with the moment of
inertia of the load.
This configuration can also be used for simple
resolvers by implementing the internal function
for positioning from an external reference point
(e.g. proximity switch).
Configuration 460 is particularly suitable for
elevators and lifting drives in general (cranes,
travelling hoists, etc.).
Configuration 210 requires the use of a speed
sensor (push-pull or line driver); this configuration
allows the most precise load control in terms of
speed and torque, including control with nominal
torque at zero rpm (standstill with torque).
Configuration 216 can be utilised for synchronous
tie applications between several motors with
definition of angular phase differences between
each axis.
Configuration 510 is the standard synchronous
motor operation. This configuration needs a
synchronous motor with Resolver and an ACT
device with EM-RES.
Configuration 515 adds the functionality of
the electronic gear to the configuration 510.
Configuration 516 allows synchronous tied
applications with an index control.
Configuration 560 adds extended brake control
and is suited especially for vertical movements.
Configurations implementable with the
ACT frequency inverter (parameter P030)